Vvr Yjvr Single Core PVC Insulated Flexible Copper Cable

Type No. of Core Nominal cross-section

Type No. of Core Nominal cross-section
Cu(AL)/XLPE(PVC)/PVC(PE)
Cu(AL)/XLPE(PVC)/ATA/PVC(PE)Cu(AL)/XLPE/AWA/PVC(PE)
1 1.5-1000
Cu(AL)/XLPE(PVC)/STA/PVC(PE)
Cu(AL)/XLPE(PVC)/SWA/PVC(PE)
2,3,4,5 1.5-400
3+1,4+1,3+2 2.5-400

Cross-section area of neutral conductor
In 3+1cores and 3+2cores should conform to specification of following table:

Nominal cross-section Main core 2.5 4 6 10 16 25 35 50
Neutral core 1.5 2.5 4 6 10 16 16 25
Nominal cross-section Main core 70 95 120 150 185 240 300 400
Neutral core 35 50 70 70 95 120 150 185

Characteristic
D.C Resistance of finished cable at 20ºC per km is not more than the following:

Nominal cross-section mm2 15 2.5 4 6 10 16 25
Cu core 12.1 7.41 4.61 3.08 1.83 1.15 0.727
Al core 18.1 12.1 7.41 4.61 3.08 1.91 1.20
Nominal cross-section mm2 35 50 70 95 120 150 185
Cu core 0.524 0.387 0.268 0.193 0.153 0.124 0.0991
Al core 0.868 0.641 0.443 0.320 0.253 0.206 0.164
Nominal cross-section mm2 240 300 400 500 630 800 1000
Cu core 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176
Al core 0.125 0.100 0.0778 0.0605 0.0469 0.0367 0.0291

Voltage test:
Each drum of finished cable should withstand power frequency voltage 3.5kV for 5 minutes,the insulation is not breakdown.
Service conditions and operation parameters of Cable:
The cable is applied to fixed installation for rated voltage 0.6/1kV of power transportation and distribution line.
Max. rated temperature of conductor. nominal operating 90ºC
Short circuit: max. for 5 sec.250ºC
The cable can be laid without drop restriction, and the environment temperature shall not be lower than 0ºC.

Standard
Our XLPE cable can be manufactured according to to IEC 60502,IEC60332,IEC60754.
Some indexes are superior to above international standard.
PS: we also can produce as per the BS, NFC, ASTM standard according to customer’s request.

Construction