BTTRZ Fire-Resistant Mineral Cable Provider

Category:

Product Standard

Product standard: 0.6/1kV and below metal sheath inorganic mineral insulated cable and terminal fire resistance test standard: BS 6387:2013 “Performance requirements for maintaining circuit integrity under fire conditions” and BS 8491:2008 “Assessment method for fire integrity of large diameter power cables for smoke and heat control systems and specific other fire safety system components”

Application Scope

This product is suitable for AC 50Hz, rated voltage not exceeding 0.6/1kV circuits. It is commonly used in high-rise buildings, subways, stations, airports, power plants, and shopping malls, which are relatively enclosed or have concentrated personnel in important buildings and facilities.

Cable Structure

Conductor

Type 1 or Type 2 copper conductor

Insulation

High-temperature resistant, non-flammable inorganic mineral insulating material (mica tape/ceramicized silicone rubber tape) with winding form

Filling

Selected according to cable specifications: glass fiber rope

Metal Sheath

Ordinary annealed copper or copper alloy, specially processed with good bending characteristics, and used as PE line

Outer Sheath

Low smoke and halogen-free plastic material with good flame retardant and protective properties

Specification Range

  • 1-core: 10~630mm²
  • 2-core: 4~150mm²
  • 3-core: 4~150mm²
  • 4-core: 4~150mm²
  • 5-core: 4~150mm²
  • 3+1-core: 4~150mm²
  • 3+2-core: 4~150mm²
  • 4+1-core: 4~150mm²

Wire Identification

  • 2-core: ● Red ● Blue
  • 3-core: ● Yellow ● Green ● Red
  • 4-core: ● Yellow ● Green ● Red ● Blue
  • 5-core: ● Yellow ● Green ● Red ● Blue ● Yellow/Green or: ● Yellow ● Green ● Red ● Blue ● White

Sheath Color

Orange (also available in customer-specified colors)

Technical Parameters

Parameter Value
Rated Voltage (U₀/U) 0.6/1kV
Maximum System Voltage (Uₘ) 1.2kV
Temperature Rating Conductor Maximum Operating Temperature: +90°C
Ambient Temperature: -20°C ~ +45°C
Cable Installation Temperature: Not below 0°C (preheating required if ambient temperature below 0°C)
Minimum Bending Radius during Installation D≤12: 6D
12≤D≤20: 10D
20≤D≤40: 15D
D>40: 20D
(Note: D is the cable outer diameter)